Tertiary Coil Pumps for Freeze Protection
I haven't seen coil pumps in a while but recently ran across them on a
job. I have the opportunity to remove them and "correct" the piping if
needed.
There are 2 air handlers with 2-way valves on their hot
water preheat coils. There is a bypass line with a check valve to
allow the coil water to circulate even if the 2-way valves are
closed. The coil has an inline tertiary pump sized for the full flow of
the coil. It runs whenever the 2-way valve is open or when ambient
drops below 35 deg F.
Similar situation on 12 other air
handlers, except they have 3-way valves. The coil pumps again run when
the valve is calling or ambient drops.
My overall task is to
convert the now constant volume hot water system (which is the secondary
side of a primary/secondary) into variable volume. I will be replacing
all 3-ways with 2-ways, adding VFD's on the pumps, etc.
So
back to my original question of the tertiary pumps. I see plenty of
installations without them, but I know they are a good backup. If the
AHU's don't already have freeze stats, I will be including them. The
job is in New Jersey.
One advantage of the pump setup: you minimize water temperature needed
to maintain the required air temperature because flow at each coil is at
the full design value at all times (conservation of Q; delta-T is lower
and m-dot is higher). Under this condition, you reduce stratification
that could cause coil freeze or freezestat trips. If you eliminate the
pump, you'll have hotter water entering at lower flow. This condition
could cause 90% of your heating to occur at the bottom 30% of your coil.
Cold air could therefore channel through the top (outlet part) of the
coil and hit a section of your freezestat.
All this said, as
walkes iterated, your secondary loop flow should be the same with or
without the coil pump and may even be marginally less, with pump work
added to fluid, reduced fluid boundary layers inside coil piping so
better heat transfer, etc.
MORE NEWS
2011-02-21